389
CompoWay/F Master Protocol Appendix B
Unit Properties Read
(Sequence No. 618 (Hex 026A))
This sequence reads the Controller/component model and communications buffer size and stores the data
starting at the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive Data Word Allocation (4th Operand of PMCR(260))
Controller Status Read
(Sequence No. 619 (Hex 026B))
This sequence reads the Controller/component status and stores the data starting at the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
Offset Contents (data format) Data
+0
Number of send data words Always 0002 hex (2 decimal)
+1
(Undefined) Node No.
(2 digits BCD)
00 to 99
First word of
send data
Number of send data words
+0
+1
(Undefined)
Node No.
Offset Contents (data format) Data
+0 Number of receive data words Always 0006 Hex (6 decimal)
+1 Response code (4 digits hex) The CompoWay/F command response code
is stored in hexadecimal code.
+2
Model number (10 digits hex The model number is stored in hexa-
decimal code.
+3
+4
(Undefined)
+5
Buffer size (4 digits hex) The send/receive buffer size is stored
in hexadecimal code.
Receive data
storage words
+0
+1
+2
Model number
Number of receive data words
Response code
+3
+4
+5
Buffer size
(Undefined)
Offset Contents (data format) Data
+0
Number of send data words Always 0002 hex (2 decimal)
+1
(Undefined) Node No.
(2 digits BCD)
00 to 99
First word of
send data
Number of send data words
+0
+1
(Undefined)
Node No.