199
Serial Gateway Overview Section 6-1
Serial Gateway Supported in Protocol Macro Mode
â–  Pre-Ver. 1.2 Units
Programming or monitoring of a serially connected PLC from the CX-Pro-
grammer during execution of a protocol macro (e.g., Host Link Master Proto-
col) requires the CX-Programmer to be directly connected to the serially
connected PLC. This configuration is not possible, however, if the serially con-
nected PLC is on a moving body connected through a serial wireless modem.
â–  Unit Ver. 1.2 or Later
The Serial Gateway can also be used in protocol macro mode. When protocol
macros are used for serial communications, the Serial Gateway is prohibited
by turning ON the Serial Gateway Prohibit Switch in the CIO Area and
enabled by turning OFF this switch. This option enables, for example, pro-
gramming or monitoring of a serially connected PLC from a CX-Programmer
that is connected to the PLC during execution of protocol macros (e.g., Host
Link Master). This function also enables continuous programming/monitoring
from the CX-Programmer when the serially connected PLC is on a moving
body connected through a serial wireless modem, making it particularly effec-
tive.
FINS
FINS
Network
Network
CS/CJ-series or CVM1/CV-series PLCs
Host Link
Network
CMND(490) instructions
Serial
FINS Network System
Serial
Serial Communications Unit/Board
with unit version 1.2 or later
Protocol
conversion
Access to PLCs used as Host
Link Slaves from personal
computers, PTs, PLCs, and
other devices by using user-
specified FINS commands is
possible.
RS-232C
CX-Programmer
RS-232C
PLC
Serial Communications Unit/Board
Serial Gateway
Serial
AGV or other moving body
WM30-S-V2 Wireless Modem
The remote PLC is on a moving body. Therefore, direct serial connection for
programming/monitoring the PLC is not possible. Access is possible, however,
by using the Serial Gateway during execution of the protocol macro.
PMCR(260)
instruction
Host Link master protocol
macro executing
WM30-S-V2 Wireless Modem
Connecting the CX-Programmer is
possible when the WM30-S-V2 is in mode
2. Connection is not possible in mode 1.
Access from CX-Programmer to
remote PLC executing protocol
macro is possible.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS1W-SCB41-V1 and is the answer not in the manual?

Omron SYSMAC CS1W-SCB41-V1 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS1W-SCB41-V1
CategoryNetwork Hardware
LanguageEnglish

Related product manuals