Page 97
P717 Exponent
This parameter is used to enter the exponent value when:
P700 PMD Type = 1 Exponent and P701 Primary M.D = 7 Others.
P718 K Factor
This parameter is used to enter the K Factor when:
P700 PMD Type = 1 Exponent and P702 Calculation = 1 Absolute see table
below for further details.
Pimary Measuring Device
P718 K
Factor
P700 = 1 Exponent
P701 = 1 Supp. Rectangular Weir
Automatically
Calculated
P700 = 1 Exponent
P701 = 2 Trapezod Weir
Automatically
Calculated
P700 = 1 Exponent
P701 = 3 Venturi Flume
Obtain value
and enter
P700 = 1 Exponent
P701 = 4 Parshall Flume
Automatically
Calculated
P700 = 1 Exponent
P701 = 5 Leopald Lagco Flume
Automatically
Calculated
P700 = 1 Exponent
P701 = 6 V Notch
Automatically
Calculated
P700 = 1 Exponent
P701 = 7 Other
Obtain value
and enter
P719 Throat Width
This parameter is used to select the Throat Width of the flume when:
P700 PMD Type = 1 Exponent and P701 = 4 Parshall Flume. After selecting
the Throat Width the Exponent P717 and K Factor P 718 will be set
automatically.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar FlowCERT LITE and is the answer not in the manual?

Pulsar FlowCERT LITE Specifications

General IconGeneral
BrandPulsar
ModelFlowCERT LITE
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals