Page 116
Date & Time
The date and time is used, to control specific relay functions and date stamp
certain events that are contained in the Data Logs. It is also used in
conjunction with the system watchdog that keeps an eye on the times the
unit has started.
P931 Date
This parameter display the current date, in the format as set by P933 (Date
Format), and can be reset if required.
P932 Time
This parameter displays the current time and can be reset if required, in the
format HH: MM (24-hour format). This is set initially at the factory for UK
time.
P933 Date Format
This parameter allows you to alter the format that the date is displayed to
your choice of DD: MM: YY, MM: DD: YY or YY: MM: DD. The default
is DD: MM: YY.
LED Colour
Each relay has an associated LED, located on the unit’s front panel, which
indicates the status of the relay. By default the LED of any relay that has
been programmed but is in its “OFF” state will be illuminated ‘yellow’.
When “ON” alarm relays will cause the LED to illuminate Red and pump,
control and miscellaneous relays will cause the LED to illuminate green.
LED’s of any relays that have not been programmed will not be illuminated.
Customised settings for the colour of LED’s can be achieved by using the
following parameters.
P935 Off Relay Colour
This parameter selects the colour that a programmed relay should be when
it is in its “OFF” state. The default is 3 = yellow, but can be changed to ‘no
colour’, red or green.
P936 Alarm Relay Colour
This parameter selects the colour that an alarm relay should be when it is in
its “ON” state. The default is 1 = red, but can be changed to ‘no colour’,
green or yellow.