Page 106
Operation
P831 mA Mode
This parameter determines how the ma Output relates to what is measured.
By default it operates exactly the same as the display (P100), but it can be
set to operate as follows:
Setpoint
By default the mA Output will represent the empty (0 or 4mA dependant
on (P830) mA Range) and 100% of the operational span (20mA), but you
may wish to have the output represent a section of the operational span. For
example, the application has an operational span of 6 feet but output is to
represent empty (0 or 4mA dependant on (P830) mA Range) to a level of
5 feet (20mA). If so P834 (Low Level) should be set to 0.00 feet and P835
(High Level) should be set to 5 feet.
P834 mA Low Value
This parameter sets, in Measurement Units (P104), the value of ‘level’,
‘distance’ or ‘space’, depending on the selected mA Out Mode (P831) at
which the low mA output will occur (0 or 4mA dependant on (P830) mA
Range)
Default = 0.000 inches
P835 mA High Value
This parameter sets, in Measurement Units (P104), the value of ‘level’,
‘distance’ or ‘space’, depending on the selected mA Out Mode (P831) at
which the high mA output will occur (20mA).
Default = 228.346 inches