Download procedure:
1. Download fi le
2. Unpack the ZIP fi le
3. Save “update.bin” on USB stick
4. Plug the USB stick into the USB port of the REMS Multi-Push
See 2.3 for the further procedure.
NOTICE
The defaults for the different test criteria (test sequences, pressures and times)
in the settings menu of the REMS Multi-Push are taken from EN 806-4:2010
or the information leafl et “Leak tests of drinking water installations with compressed
air, inert gas or water” (January 2011) of the German Central Association for
Sanitary, Heating and Air Conditioning (ZVSHK). All defaults for the test programs
can be edited by the user in the Settings menu and in the Flushing, Test with
compressed air, Test w
ith water and Compressed Air Pump programs. Changes
in the Settings menu are sav
e
d, i.e. they reappear the next time the REMS
Multi-Push is switched on. If the defaults are only changed in one of the programs,
the original defaults appear again the next time the REMS Multi-P
ush is switched
on. Reset resets all defaults to factory settings and the language to German
(deu) and the date, time, units formats to DD.MM.YYYY, 24 h, m/bar.
Att
e
ntion:
The user is solely responsible for transferred or newly entered
test criteria (test sequences, pressures and time
s) or defaults in the
individual programs and the conclusions from the tests. Especially, the
user must decide wheth
er a prescribed stabilisation/wit time is ended
and must confi rm this by \Enter.
The respective national safety provisions, rules and regulations valid for
the application site must be considered and observed.
The electronic memory of REMS Multi-Push holds 40 fi les (logs). A soon as a
program has been selected from the Start menu and the selected data have
been confi rmed with Enter, a new le no. is
created automatically even if the
program is then aborted e.g. with Esc. If the 40th memory location is occupied,
the message “Last le no. available”. After completing thi
s process, all les
should be copied to a USB stick via the USB port (Fig. 2 (33)). The oldest fi le
no. in the memory is then overwritten when further fi les are saved.
Screen display (must be released
by Enter):
000425
19.08.2013 10:13
Files 40/40
Last fi le no.
available
Consecutive fi le no. 000425
Date 19.08.2013 Time 10:13 (creation of a new fi le no.)
Files 40/40 (a max. of 40 fi les are saved)
Last fi le no.
available
3.1 F
lushing o
f drinking water installations programs
In EN 806-4:2010 and for
German
y additionally in Technical Rules – Worksheet
DVGW W 557 (A) October 2012 of the DVGW German Association of the Gas
and Water Industry e.V. and in the information leafl et “Flushing, disinfection
and commissioning of drinking water installations” (August 2014) of the German
Central Association for Sanitary, Heating and Air Conditioning (ZVSHK) the
ushing methods “fl ushing with water” and “Flushing with water/air mixture with
pressure surges” are described. REMS Multi-Push additionally offers the ushing
program “fl ushing with water/air mixture with const
ant compressed air”.
Exce
rpt from EN 806-4:2010, 6.2.1 “The drinking water installation must be
ushed with drinking water after installation and pressure testing as well as
immediately before commissioning.” “If a system is not put into operation imme-
diately after commissioning, it must be ushed at regular intervals (up to 7 days).”
3.1.1 Flushing with water program (without air supply)
3.1.1 Flushing with water program (without air supply)
In accordance with EN 806-4:
2010 and for
Germany
Germany
additionally in accordance
with the Technical Rule – Worksheet DVGW W 557 (A) October 2012 of the
DVGW German Gas and Water Association and the information leafl et “Flushing,
disinfection and commissioning of drinking water installations” (August 2014)
of the Central Association for Sanitary, Heating, Air Conditioning (ZVSHK),
Germany, the drinking water us
ed for fl ushing must be fi ltered and must be of
perfect drinking water quality. Filters must hold back particles ≥ 150 µm (Use
REMS fi ne fi lter with lter cartridge
90 µm, Art
. No. 115609).
The system must
be fl ushed section for section depending on the size of the installation and the
arrangement and lay of the pipes. Flushing must be start on the bottom fl oor
of the building and continue upwards in lines, within a line oor by oor, i.e.
from the nearest to the furthest line and fl oor. The minimum ow velocity when
ushing the installation must be 2 m/s and the water in the system must be
replaced at least 20 times during fl ushing.
Within the oor and single lines, at least as many tapping points as listed in the
following table as a recommended value for a ushing section will be fully
opened for at least 5 minutes fl oor by fl oor.
Greatest rated width of the pipe in the
ushed section, DN
25
32
40
50
Greatest rated width of the pipe in the fl ushed
section, in inches
1"
1¼"
1½"
2"
Minimum number of tapping points to be
opened DN 15 (½")
2
4
6
8
Table 1: Recommended value for the minimum number of tapping points to be
opened related to the greatest rated width of the distribution line” (single tapping
rate at least 10 l/20 s) (Information leafl et “Flushing, disinfection and commis-
sioning of drinking water installations” (August 2014) of the German Central
Association for Sanitary, Heating and Air Conditioning, lines in italics added,
limiting to DN 50). Two or more REMS Multi-Push can be connected in parallel
to fl ush greater rated widths.
REMS Multi-Push displays the achieved fl ow velocity and the achieved water
change on the screen among other things.
Program sequence ↑ ↓ (8):
1. Flush \ Enter
2. without compressed air \ Enter
3. Check default max. DN according to table 1 and change if necessary
(11) \ ↓
4. Enter water volume of the ushing section VA H
2
O (0-999 l) \ Enter (see
Fig. 6)
5. Open the water supply. The values ash as long as the minimum ow
velocity v H
2
O = 2 m/s and the water change n H
2
O = 20 have not been
reached. On reaching the values \ Enter
(If the defaults v H
2
O and n H
2
O are not reached: \ Esc = cancel, clarify the
cause, repeat the process)
6. Display screen: Water pressure (p H
2
O), minimum ow velocity (v H
2
O),
ushing time (t H
2
O), water change (n H
2
O), volume of used water (V H
2
O)
\ Enter
7. Esc >> Start menu \ Memory Manager, data transfer >> 3.8.
3.1.2 Flush with water/air mixture with intermittent compressed air program
3.1.2 Flush with water/air mixture with intermittent compressed air program
The cleaning effect by fl ushing can be reinforced by adding compressed air. In
accordance with EN 806-4:2010 and information leafl et “Flushing, disinfection
and commissioning of drinking water installations” (August 2014) of the German
Central Association for Sanitary, Heating and Air Conditioning (ZVSHK), the
drinking water used for ushing must be ltrated whereby particles 150 µm
must be held back and the water must be perfectly t for drinking (REMS ne
lter with lter cartridge 90 µm, Art. No. 115609). “The pipe system can be ushed
under pressure with a drinking water/air mixture intermittently with a minimum
ow velocity in every pipe section of 0.5 m/s. A certain minimum number of tap
ttings must be opened for this. If the minimum volume fl ow is not reached with
full fi lling of the distribution pipe in a section of the pipe system to be fl ushed, a
storage tank and a pump must be used for ushing.” “The system must be ushed
section by section depending on the size of the installation and the lay of the
pipes. No fl ushing section may exceed a pipe section length of 100 m.”
Greatest rated width of the pipe in the fl ushed
section, DN
25
32
40
50
Greatest rated width of the pipe in the fl ushed
section, in inches
1"
1¼"
1½"
2"
Minimum volume fl ow with fully fi lled pipe
section, in l/min
15
25
38
59
Minimum number of DN 15 (½") tapping
points to be opened fully or a corresponding
cross-sectional area
1
2
3
4
Table 2: Recommended minimum ow
and minimum number of tapping points
depending on the greatest ra
ted diameter of the pipe in the ushed section
which must be opened for the ushing process (for a minimum ow velocity of
0.5 m/s) (EN 806-4:2010, lines in italics added, limiting to DN 50). Two or more
REMS Multi-Push can be connected in parallel to fl ush gr
eater rated widths.
The manual actuation o
f the setting ttings for the supply of intermittent
compressed air described in EN 806-4:2010 and in the information leafl et
“Flushing, Disinfe
ction and Commissioning of Drinking Water Installations”
(August 2014) of the German Central Association for Sanitary, Heating and Air
Conditioning (ZVSHK) takes place automatically in REMS Multi-Push. The
compressed air is fed with an exces
s pressure of 0.5 bar above the measured
water pressure. The compressed
air supply lasts 5 s, the stagnation phase
(without compressed air) lasts 2 s.
REMS Multi-Push displays the achieved ow velocity and the achieved volume
ow on the screen among other things.
Program sequence ↑ ↓ (8):
1. Flush \ Enter
2. Intermittent compressed air \ Enter
3. Check default max. DN according to table 2 and change if necessary
(11) \ ↓
4. Enter water volume of the ushing section VA H
2
O (0-999 l) (11) \ Enter
(see Fig. 6)
5. Open the water supply. If the minimum fl ow velocity v H
2
O = 0,5 m/s, the
minimum volume fl ow VS H
2
O and the fl us
hing time are reached \ Enter
The ushing time (according to information leafl et T 84-2004 “Flushing,
Disinfection and Commissioning of Drinking Water Installations” of the
German Central Association for Sanitary, Heating and Air Conditioning)
depends on the pipe length and should not drop below 15 s per metre. The
ushing time must be at least 2 minutes per tapping point.
(If the defaults v H
2
O and VS H
2
O are not reached: \ Esc = cancel, clarify
the cause, repeat the process)
6. Display screen: Water pressure (p H
2
O), minimum ow velocity (v H
2
O),
ushing time (t H
2
O), volume of use
d water (V H
2
O), volume ow (VS H
2
O)
\ Enter
7. Esc >> Start menu \ Memory Manager, data transfer >>
3.8.
24

Table of Contents

Other manuals for REMS Multi-Push SL