EasyManuals Logo
Home>Rinstrum>Measuring Instruments>5200

Rinstrum 5200 User Manual

Rinstrum 5200
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Rinstrum - 5200 Communications Manual Rev 1.2
Page 46 0025-605-120
2.4.34. SER: Set Serial Communications Settings
This is used to set the serial mode settings for each serial port.
General Details
No. of Parameters Save Changes Changes Used Increment Trade Counter
7 With TDD1 Immediately No
Parameter Details
Parameter Description Range Default Required
1 Port Number 0
1
Serial 1
Serial 2
- Yes
Serial 1 Serial 2 2 Mode
0
1
2
3
OFF
ON (low)
ON (high)
Network
0
1
OFF
ON (low)
0 No
3 Format
(ON modes
only)
0
1
2
3
4
5
6
7
8
Auto A
Auto B
Auto C
Auto D
Auto E
Print A
Print B
Print C
Custom
0 No
4 Auto source 0
1
2
3
Displayed Reading
Gross Reading
Net Reading
Full Display
0 No
5 Auto Start
Character
0 to 255 (ASCII code) 2 No
6 Auto End
Character 1
0 to 255 (ASCII code) 3 No
7 Auto End
Character 2
0 to 255 (ASCII code) 0 No
Example
Command Response Details
S01; Select Instrument 1
SER?1; 1,0,0,0,2,3,0 CRLF Query Serial 2 settings
SER1,1,5; 0 CRLF Set for Print Format A
TDD1; 0 CRLF Save Setting

Table of Contents

Other manuals for Rinstrum 5200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rinstrum 5200 and is the answer not in the manual?

Rinstrum 5200 Specifications

General IconGeneral
BrandRinstrum
Model5200
CategoryMeasuring Instruments
LanguageEnglish