Rinstrum - 5200 Communications Manual Rev 1.2
Page 50 0025-605-120
2.4.38. TAS: Gross/Net
Select Gross or Net weight display.
General Details
No. of Parameters Save Changes Changes Used Increment Trade Counter
1 Automatic Immediately No
Parameter Details
Parameter Description Range Default Required
1 Gross/Net 0
1
Net
Gross
- No
Example:
Command Response Details
S01;
MSV?; 00200.0 CRLF Query current weight
TAS?; 0 CRLF Instrument is in net mode
TAS1; 0 CRLF Switch to gross weight
MSV?; 00400.0 CRLF Query current weight
TAS?; 1 CRLF Instrument is in gross mode