Publication 2098-IN005C-EN-P — March 2008
Troubleshooting Your Ultra3000 Servo Drive 111
Scanner Problems
If using a scanner, check the scan list, data rate, and addresses of
devices. Verify series and revision of the scanner is the latest. If the
scanner is bus-off, recycle the 24V supply and then reset the scanner.
If the scanner goes bus-off again, the problem is some combination of
these issues.
Defective node device
Incorrect node data rate
Bad network topology
Faulty wiring
Faulty scanner
Faulty power supply
Bad grounding
Electrical noise
Power Supply Problems
If a single power supply is used, add up the current requirements of
all devices drawing power from the network. This total should be
considered the minimum current rating in selecting the power supply
used.
In addition, check these symptoms.
Length and current level in trunk and drop cables
Size and length of the cable supplying power to the trunk
Voltage measured at the middle and ends of the network
Noise in network power measured with an oscilloscope

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley Ultra3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley Ultra3000 and is the answer not in the manual?

Rockwell Automation Allen-Bradley Ultra3000 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley Ultra3000
CategoryServo Drives
LanguageEnglish

Related product manuals