142 Publication 2711P-UM001I-EN-P - December 2008
Chapter 6 Install and Replace Components
Component Compatibility
for PanelView Plus CE
Terminals
It is important to match the series of the internal CompactFlash card
with the correct series of the logic module and software version. The
series of the CompactFlash determines the version of FactoryTalk
View ME software and version of the operating system. The logic
module is available with or without memory installed.
Component Compatibility
for PanelView Plus
Terminals
It is important that you match the series of the internal CompactFlash
card with the correct series of the logic module and software revision.
The series of the CompactFlash determines the version of FactoryTalk
View ME software. The logic module is available with or without
memory installed.
Logic Module
6189-RPx, 6189-RPRHx,
6189-RPEHx,
2711P-RPx, 2711P-RPx,
2711P-RP6x, 2711P-RP7x
Internal CompactFlash
6189-RW2, -RW3, -RW4
2711P-RW6, -RW7, -RW8
FactoryTalk View ME
& OS Software Version
Series A: 6189-RPxH/A
(1)
(1)
When upgrading from FactoryTalk View ME software, version 3.0 to 3.10 or later, the Firmware Upgrade Kit is recommended.
Series B: 6189-RWx/B FactoryTalk View ME 3.0
Windows CE 3.0
Series B: 6189-RPxH/B Series C: 6189-RWx/C FactoryTalk View ME 3.10
Windows CE 4.1
Series B: 6189-RPxH/B
Series C: 6189-RPxH/C
Series D: 6189-RPxH/D
Series E: 6189-RPxHx/E
Series F: 2711P-RPxx/F
(2)
Series G: 2711P-RPxxx/G
(2)
Series H: 2711P-RPxxx/H
(2)
(2)
Series F and later logic modules work with PanelView Plus and PanelView Plus CE CompactFlash cards.
Series D: 6189-RWx/D
Series E: 6189-RWx/E
FactoryTalk View ME 3.20
Windows CE 4.1
Series F: 6189-RWx/F
Series G: 6189-RWx/G
Series H: 2711P-RWx/H
FactoryTalk View ME 4.0
Windows CE 4.1
Series J: 2711P-RWx/J FactoryTalk View ME 5.0
Windows CE 4.1
Logic Module
2711P-RPx, 2711P-RP1x,
2711P-RP2x, 2711P-RP3x
Internal
CompactFlash
2711P-RW1, -RW2,
-RW3
FactoryTalk View ME
Software Version
Series A: 2711P-RPx/A
(1)
(1)
Series A logic modules are compatible with series B Compact Flash cards. When upgrading from FactoryTalk View ME software,
version 3.0 to 3.10 or later, the Firmware Upgrade Kit is required.
Series B: 2711P-RWx/B FactoryTalk View ME 3.0
Series B: 2711P-RPx/B Series C: 2711P-RWx/C FactoryTalk View ME 3.10
Series B: 2711P-RPx/B
Series C: 2711P-RPx/C
Series D: 2711P-RPx/D
Series E: 2711P-RPxx/E
Series F: 2711P-RPxx/F
(2)
Series G: 2711P-RPxxx/G
(2)
Series H: 2711P-RPxxx/H
(2)
(2)
Series F and later logic modules work with PanelView Plus and PanelView Plus CE CompactFlash cards.
Series D: 2711P-RWx/D
Series E: 2711P-RWx/E
FactoryTalk View ME 3.20
Series F: 2711P-RWx/F
Series G: 2711P-RWx/G
Series H: 2711P-RWx/H
FactoryTalk View ME 4.0
Series J: 2711P-RWx/J FactoryTalk View ME 5.0

Table of Contents

Other manuals for Rockwell Automation PanelView Plus Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PanelView Plus Series and is the answer not in the manual?

Rockwell Automation PanelView Plus Series Specifications

General IconGeneral
BrandRockwell Automation
ModelPanelView Plus Series
CategoryTouch terminals
LanguageEnglish

Related product manuals