PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
3-18 Programming and Parameters
MOTOR CONTROL
Torq Attributes
750 [TrqTpr_Enable]
Enables/Disables the current/speed function. The current/speed
function allows you to change the current limits set in Pars 8
[Current Lim Pos] and 9 [Current Lim Neg] by setting up to five
setpoints using parameters [TrqTpr_Limx] and a threshold
speed in Par 756 [TrqTpr_Spd].
“Disabled” = The limits current /speed curve is disabled
“Enabled” = The limits current /speed curve is enabled
Default:
Options:
0 =
0 =
1 =
“Disabled”
“Disabled”
“Enabled”
751,
752,
753,
754,
755,
756
751 [TrqTpr_Lim0]
The current limit of the current/speed curve that operates
constantly up to the speed set in Par 756 [TrqTpr_Spd]. The
value specified in this parameter overrides the values specified
in Pars 8 [Current Limit Pos] and 9 [Current Lim Neg].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
752 [TrqTpr_Lim1]
First reduced current limit of the current/speed curve. The value
defined in this parameter must be less than the value in Par 751
[TrqTpr_Lim0] and greater than the values in Pars 753
[TrqTpr_Lim2], 754 [TrqTpr_Lim3] and 755 [TrqTpr_Lim4].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
753 [TrqTpr_Lim2]
Second reduced current limit of the current/speed curve. The
value defined in this parameter must be less than the value in
Par 752 [TrqTpr_Lim1] and greater than the values in Pars 754
[TrqTpr_Lim3] and 755 [TrqTpr_Lim4].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
754 [TrqTpr_Lim3]
Third reduced current limit of the current/speed curve. The value
defined in this parameter must be less than the value in Par 753
[TrqTpr_Lim2] and greater than the value in Par 755
[TrqTpr_Lim4].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
755 [TrqTpr_Lim4]
Last reduced current limit of the current/speed curve. The value
defined in this parameter must be less than the value in Par 754
[TrqTpr_Lim3]. The drive will operate at this current limit up to
the value set in parameter 162 [Max Feedback Spd].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
756 [TrqTpr_Spd]
Threshold speed at which torque reduction begins, as
determined by the current/speed curve.
Default:
Min/Max:
Units:
0
0 / Par 162
RPM
750,
756
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
A
Par 10 [Cur Lim Pos Out]
or
Par 11 [Cur Lim Neg Out]
T
rqTpr_Lim0]
Current/Speed
Par 162 [Max Feedback Spd]
T
rqTpr_Lim1]
T
rqTpr_Lim2]
T
rqTpr_Lim3]
T
rqTpr_Lim4]
Par 756 [TrqTpr_Spd]
A
A
A
A
A
A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex series and is the answer not in the manual?

Rockwell Automation PowerFlex series Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex series
CategoryDC Drives
LanguageEnglish

Related product manuals