MOTOR CONTROL
Torq Attributes
750 [TrqTpr_Enable]
Enables/Disables the current/speed function. The current/speed
function allows you to change the current limits set in Pars 8
[Current Lim Pos] and 9 [Current Lim Neg] by setting up to five
setpoints using parameters [TrqTpr_Limx] and a threshold
speed in Par 756 [TrqTpr_Spd].
• “Disabled” = The limits current /speed curve is disabled
• “Enabled” = The limits current /speed curve is enabled
Default:
Options:
0 =
0 =
1 =
“Disabled”
“Disabled”
“Enabled”
751,
752,
753,
754,
755,
756
751 [TrqTpr_Lim0]
The current limit of the current/speed curve that operates
constantly up to the speed set in Par 756 [TrqTpr_Spd]. The
value specified in this parameter overrides the values specified
in Pars 8 [Current Limit Pos] and 9 [Current Lim Neg].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
752 [TrqTpr_Lim1]
First reduced current limit of the current/speed curve. The value
defined in this parameter must be less than the value in Par 751
[TrqTpr_Lim0] and greater than the values in Pars 753
[TrqTpr_Lim2], 754 [TrqTpr_Lim3] and 755 [TrqTpr_Lim4].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
753 [TrqTpr_Lim2]
Second reduced current limit of the current/speed curve. The
value defined in this parameter must be less than the value in
Par 752 [TrqTpr_Lim1] and greater than the values in Pars 754
[TrqTpr_Lim3] and 755 [TrqTpr_Lim4].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
754 [TrqTpr_Lim3]
Third reduced current limit of the current/speed curve. The value
defined in this parameter must be less than the value in Par 753
[TrqTpr_Lim2] and greater than the value in Par 755
[TrqTpr_Lim4].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
755 [TrqTpr_Lim4]
Last reduced current limit of the current/speed curve. The value
defined in this parameter must be less than the value in Par 754
[TrqTpr_Lim3]. The drive will operate at this current limit up to
the value set in parameter 162 [Max Feedback Spd].
Default:
Min/Max:
Units:
0
0 / 200
%
750,
756
756 [TrqTpr_Spd]
Threshold speed at which torque reduction begins, as
determined by the current/speed curve.
Default:
Min/Max:
Units:
0
0 / Par 162
RPM
750,
756
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
A
Par 10 [Cur Lim Pos Out]
or
Par 11 [Cur Lim Neg Out]
rqTpr_Lim0]
Current/Speed
Par 162 [Max Feedback Spd]
rqTpr_Lim1]
rqTpr_Lim2]
rqTpr_Lim3]
rqTpr_Lim4]
Par 756 [TrqTpr_Spd]
A
A
A
A
A
A