Exchange of configuration data with STEP7
6.2 Message: SINEMA configuration not yet accepted
SCALANCE SC-600 Web Based Management (WBM)
354 Configuration Manual, 10/2021, C79000-G8976-C475-03
Importing configuration data via STEP 7 Basic/Professional
To import configuration data via STEP 7 Basic/Professional, follow these steps:
1. Open the relevant STEP 7 project in STEP 7 Basic/Professional.
2. Open the project view.
3. Open the network view or the topology view.
4. Open the Hardware catalog.
5. In the hardware catalog, navigate to the device with the relevant article number.
6. Select the desired device with a mouse click.
7. Set the matching firmware version via the drop-down list of the hardware catalog.
8. Drag-and-drop the device to the network view or to the topology view.
9. Select the device in the network view on in the topology view.
10. In the Inspector window, navigate to the "Management" parameter under "Properties >
General".
11. In the parameter group "Load / save file", click the "Load from file" button.
12. Select the desired file.
13. Click the "Open" button.
The "Load configuration file" dialog opens.
14. Enter the password for the decryption of the file.
Note
You assign this password in the WBM under "System > Load&Save > Passwords".
15. Click the "OK" button.
6.2 Message: SINEMA configuration not yet accepted
When the following message is displayed in the display area an error has occurred
transferring the configuration from STEP 7 Basic / Professional as of V13 to the device:
"SINEMA Configuration not accepted yet. With restart of device, all configuration
changes will be lost."
One possible cause is, for example, that during transfer the device was not reachable.
If you now change a parameter directly on the device (WBM/CLI/SNMP) these changes
are lost when the device restarts.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET SCALANCE SC646-2C and is the answer not in the manual?

Siemens SIMATIC NET SCALANCE SC646-2C Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET SCALANCE SC646-2C
CategorySwitch
LanguageEnglish

Related product manuals