Description of system components
8.3 Operator panel with display
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
125
Parameters
Range
Note
Trip level
0.00 - 40.00 A
-
Warning level
0.00 - 40.00 A
-
0/4-20 mA monitoring → 0/4-20 mA limits
Possible only if analog module 1 and/or 2 is
configured
Analog module 1 - trip level
0/4-20 mA > (upper limit)
0 - 255 Represented in 0/4 - 20 mA similar to
"Measured values" menu
Analog module 1 - warning level
0/4-20 mA > (upper limit)
0 - 255 Represented in 0/4 - 20 mA similar to
"Measured values" menu
Analog module 1 - trip level
0/4-20 mA < (lower limit)
0 - 255 Represented in 0/4 - 20 mA similar to
"Measured values" menu
Analog module 1 - warning level
0/4-20 mA < (lower limit)
0 - 255 Represented in 0/4 - 20 mA similar to
"Measured values" menu
Analog module 2 - trip level
0/4-20 mA > (upper limit)
0 - 255 Represented in 0/4 - 20 mA similar to
"Measured values" menu
Analog module 2 - warning level
0/4-20 mA > (upper limit)
0 - 255 Represented in 0/4 - 20 mA similar to
"Measured values" menu
Analog module 2 - trip level
0/4-20 mA < (lower limit)
0 - 255 Represented in 0/4 - 20 mA similar to
"Measured values" menu
Analog module 2 - warning level
0/4-20 mA < (lower limit)
0 - 255 Represented in 0/4 - 20 mA similar to
"Measured values" menu
Temperature monitoring → temperature limits
Possible only if temperature module 1 and/or 2 is
configured
Temperature module 1 -
trip level > (upper limit)
0 - 65,535 K Represented in °C/F similar to "Measured values"
menu
Temperature module 1 -
warning level > (upper limit)
0 - 65,535 K Represented in °C/F similar to "Measured values"
menu
Temperature module 2 -
trip level > (upper limit)
0 - 65,535 K Represented in °C/F similar to "Measured values"
menu
Temperature module 2 -
warning level > (upper limit)
0 - 65,535 K Represented in °C/F similar to "Measured values"
menu
Limit monitor - limit monitor limit
0 - 65535
-
Limit 1
0 - 65535
-
Limit 2
0 - 65535
-
Limit 3
0 - 65535
-
Limit 4
0 - 65535
-
Limit 5
0 - 65535
-
Limit 6
0 - 65535
-
Note
Password protection
It is only possible to change these parameters if password protection is not active. Only then
can you choose the parameter to be modified with the "OK" button.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro V EIP and is the answer not in the manual?

Siemens SIMOCODE pro V EIP Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro V EIP
CategoryControl Unit
LanguageEnglish

Related product manuals