Compartment identification
9.6 Alarm, fault, and system events for compartment identification
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
171
9.6 Alarm, fault, and system events for compartment identification
Messages
Table 9- 1 Alarm, fault, and system events
Message
Description
Troubleshooting
Initialization module write-protected The initialization module is completely
write-protected.
Deactivate write protection of the
initialization module.
Initialization module write-protected,
parameter changes not allowed
The initialization module is completely
or partially write-protected.
Reparameterization of SIMOCODE pro
is denied because the initialization
module is write-protected.
Deactivate write protection of the
initialization module.
Initialization module identification data
write-protected
The device addressing and the I&M
data in the initialization module are
write-protected. Parameterization will
only be accepted by SIMOCODE if the
new parameter set is identical to the
data stored in the initialization module
at that time.
• Select a parameterization with
identical addressing and I&M data
• Deactivate the partial write
protection of the initialization
module.
Initialization module read in The parameters of the initialization
module were read into SIMOCODE.
-
Initialization module programmed The reparameterization was accepted
in the initialization module.
-
Initialization module cleared The initialization module has been
cleared and is now back in the as-
delivered condition.
-

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro V EIP and is the answer not in the manual?

Siemens SIMOCODE pro V EIP Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro V EIP
CategoryControl Unit
LanguageEnglish

Related product manuals