Commissioning, service, troubleshooting
13.2 Commissioning
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
257
13.2 Commissioning
13.2.1 Commissioning with PROFIBUS
13.2.1.1 PROFIBUS commissioning steps
Please observe the information in Chapter General information about commissioning and
service (Page 255).
To commission SIMOCODE pro, proceed as follows:
Table 13- 2 Commissioning the basic unit
1 Switch on the power supply. In a fault-free state, the following LEDS should light up or flash green:
• "Device" (lights up)
• "Bus" if PROFIBUS DP is connected (lights up or flashes).
Proceed to Step 2.
Otherwise, carry out diagnostics according to the LED display. For more information, see Chapter
Diagnostics via
LED display on the basic unit and on the operator panel (PROFIBUS) (Page 259). Try to rectify the fault.
2 If you wish to make SIMOCODE pro available on the PROFIBUS DP, set the PROFIBUS DP address. For more
information, see Chapter Setting the PROFIBUS DP address (Page 258).
3 Parameterize SIMOCODE pro or check the existing parameterization, e.g. with a PC on which SIMOCODE ES (TIA
Portal) software is installed. For this, connect the PC / PG to the system interface with the PC cable (see the figure
below).
With SIMOCODE pro C use the system interface on the front and with SIMOCODE pro S use the right-hand system
Figure 13-1 Connecting a PC to the basic unit