12.3.1 Information about the system interfaces
Information about the system interfaces
SIMOCODE pro system components are connected to each other via the system
interfaces. The system interfaces are provided on the front and bottom of the devices.
Connecting cables of different lengths are available for connecting the system
components.
The PC cables, addressing plugs, and memory modules can be plugged directly into the
system interface.
The system is always configured according to the basic unit. Basic units have two system
interfaces:
Bottom/left: For outgoing connecting cable to the current or current / voltage
measuring module.
Front side: For outgoing connecting cables leading to an expansion module or
operator panel, or for PC cables, memory modules or addressing plugs.
Current measuring modules and current / voltage measuring modules have one system
interface:
Bottom or front: For incoming connecting cable from the basic unit.
Expansion modules have two interfaces on the front:
Left: For incoming connecting cables from the upstream expansion module or
SIMOCODE pro S/SIMOCODE pro V basic unit.
Right: For outgoing connecting cables leading to an expansion module or operator
panel, and for PC cables, memory modules or addressing plugs.
Decoupling modules have 2 interfaces on the front:
Left: For incoming connecting cable from the upstream expansion module or basic
unit.
Right: Exclusively for the outgoing connecting cable to the current / voltage measuring
module.
Operator panels have two system interfaces:
Front side: For PC cables, memory modules and addressing plugs.
Rear side: For incoming connecting cable from the upstream expansion module or
basic unit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro V EIP and is the answer not in the manual?

Siemens SIMOCODE pro V EIP Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro V EIP
CategoryControl Unit
LanguageEnglish

Related product manuals