Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
137
Response to warning level
Here you can define how SIMOCODE pro will respond if the warning level is overshot.
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Table 4- 35 "Warning level" response for monitoring current limits I >
Response
Warning level
Deactivated
X (d)
signal X
warn
X
tripping
Delay
0 to 25.5 s (default: 0.5 s)
Hysteresis
Here you can set the hysteresis for the current limits I> (upper limit):
Hysteresis
0 to 15% of the level value in steps of 1%
Default setting: 5 %