Parameters
4.5 Inputs
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
197
4.5.8
Acyclic Receive
Description
In addition to "Cyclic Receive", it is possible to transfer further data acyclically to
SIMOCODE pro via PROFIBUS DP. With the "Acyclic receive" function block, you can
specify which acyclic information from the PROFIBUS DP will be further processed in
SIMOCODE pro. With the "Acyclic receive" function block, you can specify which information
will be further processed in SIMOCODE pro.
The "Acyclic receive" function blocks consist of:
Eight bits each (byte 0 and byte 1 for binary information)
One word (= two bytes, byte 2 to 3 for an analog value, freely parameterizable).
Overall there are three "Acyclic receive" function blocks (0, 1, 2/3)
Schematic
The following schematic shows the "Acyclic receive" function blocks:
Figure 4-70 Function schematic of acyclic receive data
Acyclic services
Acyclic data are transferred only on request.
The information (4 bytes) can be found in data record 202. This data record can be written
by every master (PLC or PC) that supports the acyclic services of PROFIBUS DPV1.
Connection monitoring is activated every time the data record is received. The content of the
data record is deleted after a 5-second time-out has elapsed.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals