Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
152 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
4.3.7.2
Operating hours monitoring
Motor operating hours monitoring - use
The motor operating hours monitoring function enables the operating hours (service life) of a
motor to be recorded so that motor maintenance prompts can be generated in good time as
applicable.
Level
If the operating hours exceed the set response level, the monitoring function responds.
Level
0 to 1193046 hours (default: 0 h)
Active status
Unless deactivated, this function is always active, independent of whether the motor is
running or not (operating state "ON").
Response
You can define the response to overshoot here.
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7) and Table "Responses" in Chapter Description of functions of operation monitoring
(Page 150).

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000