Parameters
4.7 Standard functions
SIMOCODE pro - Parameterize
208 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
4.7.3
Test position feedback (TPF)
Description
You can carry out the "Cold run" function test using the "Test Position Feedback (TPF)"
function block. For this purpose, the function block input (plug) must be connected to the
respective socket. The activated test position will be indicated by the flashing QL of the
control function.
The "Test Position Feedback (TPF)" function block consists of
one plug
a "Status - test position" socket. It is set if a signal is pending at the input.
one "Fault - test position feedback error" socket. It is set when
"TPF" is activated although current is flowing in the main circuit
"TPF" is activated and current is flowing in the main circuit.
In total, one "Test Position Feedback" function block is available.
Note
When the test position is enabled, the QLE
/ QLA sockets of the control function are
activated, to indicate test operation of the motor feeder via a flashing button LED, for
example
.
Schematic
The following schematic shows the "Test Position Feedback" function block:
Figure 4-77 "Test Position Feedback" function block

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals