Parameters
4.8 Logic modules
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
265
4.8.13
Calculators (calculation modules) 3, 4
Description
Using the "Calculator 3" and "Calculator 4" function blocks (for SIMOCODE pro V PN and
pro V EIP basic units only), analog values can be processed according to the following
arithmetic:
Output = Input 1 [Operator 1] Input 2 [Operator 2] Input 3 [Operator 3] Input 4.
You can connect the corresponding analog signals to the 4 inputs "Calculator 3/4 - Inputs 1
to 4". As operators "Calculator 3/4 - Operator 1 to 3," you can choose one of the four
standard operators ("+", "-", "*," or "/").
With "Calculator 3/4 - Priority 1 to 3," you can specify the processing sequence (high,
medium, low). You must clearly define a priority for each operator. The priority determines
the processing sequence comparable to the placement of a term inside parentheses.
Example:
Output = I1 OP1 I2 OP2 I3 OP3 I4, where
OP1 = "*"; Medium,
OP2 = "+"; High,
OP3 = "-"; Low
Associated equation: Output = (I1 * (I2 + I3)) - I4.
If you interconnect the input to the device-internal analog output data element "Output 1 -
Fixed level", the input is assigned the constant "Const x" (x = 1 - 4). In this case, the
respective edit field for the constant is activated. You can enter a value between 0 and
65535.
The "Calculator 3" and "Calculator 4" function blocks each consist of:
Four analog plugs
One analog socket
Logic.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000

Related product manuals