Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
136 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
I> (upper limit)
Trip level, warning level
When monitoring current limits I > (upper limit), two different response levels can be
parameterized and monitored: I> (upper limit) trip level, I> (upper limit) warning level
If the current of one or more phases exceeds the response level, current limit monitoring
responds.
0 to 1020 % of l
s
in steps of 4% (default: 0)
0 to 1020 % of l
s
in steps of 4% (default: 0)
Active status of trip and warning levels
The trip level / warning level is active only when the motor is running, the startup procedure
has been completed and there is no test position feedback (TPF) (run+).
Here you can define how SIMOCODE pro will respond if the trip level is undershot.
See also "Tables of responses of SIMOCODE pro" in Chapter Important information
(Page 7).
Table 4- 34 "Trip level" response for monitoring current limits I >
Deactivated X (d)
0 to 25.5 s (default: 0.5 s)