Parameters
4.3 Monitoring functions
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
149
Response to trip level 0/4 to 20 mA > (upper limit), 0/4 to 20 mA < (lower limit)
Here, you can define the response of SIMOCODE pro in the event that the monitored
variable overshoots/undershoots the set trip level:
For further information, see also "Tables of responses of SIMOCODE pro" in Chapter
Important information (Page 7).
Table 4- 44 "Trip level" response for 0/4 to 20 mA monitoring
Response
Trip level
disabled
X (d)
signaling X
warn
tripping
X
delay
0 to 25.5 s (default: 0.5 s)
Response to warning level 0/4 to 20 mA > (upper limit), 0/4 to 20 mA < (lower limit)
Here, you can define the response of SIMOCODE pro in the event that the monitored
variable overshoots/undershoots the set warning level:
For further information, see also "Tables of responses of SIMOCODE pro" in Chapter
Important information (Page 7).
Table 4- 45 "Warning level" response for 0/4 to 20 mA monitoring
Response
Warning level
disabled
X (d)
signaling
X
warn
X
tripping
delay
0 to 25.5 s (default: 0.5 s)

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals