Parameters
4.4 Outputs
SIMOCODE pro - Parameterize
176 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
3) Output of any analog value from the automation system cyclically via the communication
bus
One word (2 bytes) can be transmitted cyclically from the automation system to
SIMOCODE pro via PROFIBUS; two words (2 times 2 bytes) can be transmitted via
PROFINET. Any value can be output as a 0/4 to 20 mA signal by directly connecting this
cyclic control word to the analog module output. If the transmitted value is in S7 Format
(0 to 27648), this must be taken into consideration when parameterizing:
Figure 4-55 Output of an analog value from the automation system
As a result,
● The "Start value of value range" to be selected is: 0
● The "End value of value range" to be selected is: 27648.
When the parameterized "Output signal" = 0 to 20 mA
● 0: 0 mA at the analog module output
● 27648: 20 mA at the analog module output.
When the parameterized "Output signal" = 4 to 20 mA
● 0: 4 mA at the analog module output
● 27648: 20 mA at the analog module output.