Parameters
4.6 Analog value recording
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
201
The following schematic shows the "Analog Value Recording" function block:
Figure 4-73 Schematic of the "Analog Value Recording" function block
Table 4- 66 "Analog value recording" settings
Trigger input Activate analog value recording with any signal
(any socket ,
e.g. device inputs, current flowing)
Any value (1 word / 2 bytes) in SIMOCODE pro
Trigger edge positive (default)
/ negative
0.1 to 50 s, in steps of 0.1 s (default: 0.1 s)
0 to 100 % in steps of 5 % (default: 0 %)
Record the motor current when the motor starts / sampling time = 12 s / pre-trigger = 25 %
(3 s):
Figure 4-74 Application example of the analog value recording