Parameters
4.7 Standard functions
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
205
Testing
Testing can be carried out as follows:
Via the "TEST / RESET" button on the basic unit and on the operator panel (can be
deactivated), as well as via PC with SIMOCODE ES software.
Via the plugs of the internal "Test 1" or "Test 2" function blocks
Via the menu of the operator panel with display (e.g. the "Commands" menu item).
Testing can be terminated at any time - it does not influence the thermal motor model of the
overload function, i.e. after switching off via test, the system can be reset immediately.
Tripping only occurs for Test 1 when the operating mode is set to "Remote."
Reset function
Resetting can be carried out as follows:
Via the "TEST / RESET" button on the basic unit and on the operator panel (can be
deactivated), as well as via PC with SIMOCODE ES software.
Using the "Reset input" plug of the internal function blocks via the plugs of the internal
function blocks "Reset 1," "Reset 2," and "Reset 3."
Via the menu of the operator panel with display (e.g. the "Commands" menu item).
The "Reset" function block consists of one plug.
There are three function blocks "Reset 1" to "Reset 3."
All reset inputs (sockets) have equal priority (or function).
Test function
A SIMOCODE pro function test can also be initialized via the test function. The test function
comprises the following steps:
Lamp / LED test (test function activated for < 2 s)
Test of the device functionality (test function activated for 2 to 5s)
Switching off the QE (test function activated for > 5 s). The QE can only be switched off
using the "Test 1" function block and in the "Local 1-3" operating mode using the
"TEST/RESET" button on the basic unit / operator panel.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals