Parameters
4.7 Standard functions
SIMOCODE pro - Parameterize
222 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
Settings of the DIP switches on the DM-F Local
Table 4- 78 Settings of the DIP switches (DM-F Local)
Switch setting
OFF / ON
1
With /without cross-circuit detection
2 1 NC + 1 NO evaluation / 2 NC
evaluation
3
2x 1-channel / 1x 2-channel
4 Debounce time for sensor inputs
50 ms / 10 ms
5 Sensor input automatic start /
monitored start
6 Cascading input automatic start /
monitored start
7
With / without startup testing
8 With automatic starting / without
automatic starting after power failure
Note
The target setting of the DIP switches in the SIMOCODE
ES user interface (can be made
using the mouse pointer) is transferred to the basic unit on download but does not affect the
function of the DM
-F Local digital module. The desired function is thus saved as soon as the
parameterization has been created.
You must set the effective parameterization via the DIP switches on the front of the DM
-
F
Local (see table below and/or the manual "SIMOCODE pro Safety fail-
safe digital modules
(
http://support.automation.siemens.com/WW/view/en/50564852)"). The basic unit compares
the target setting (from the download) with the actual setting on the DM
-F Local. If these
differ, "Configuration deviati
on" is output!

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals