Settings Pulse Width Modulator
Table 4- 103 Settings Pulse Width Modulator
Pulse width modulator
Description
Input
Activation by any analog signal or "Fixed value"
Constant input Any constant; range: 0 to 65535 (default: 0)
Input Minimum
Any constant; range 0 to 65535 (default: 0)
Input Maximum
Any constant; range 1 to 65535 (default: 65535)
PWM duration
0.2 - 6553.5 s (default: 2)
Pulse width modulator formulas
Length of 1-signal = PWM period * (PWM Input - PWM Input Minimum)/(PWM Input
Maximum - PWM Input Minimum)
Length of 0-signal = PWM period - Length of 1-signal.
Note
Signal duration
The shortest signal duration for 0 and 1 is 0.1
s in each case.
If a duration for the 1 signal that is shorter than 0.1 s results from calculation, the output
will remain permanently 0, while for a duration for the 0 signal
shorter than 0.1 s the
output remains permanently 1.

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals