Introduction
1.1 Important information
SIMOCODE pro - Parameterize
8 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
SIMOCODE pro response tables
Specific responses (deactivated, signaling, warning, tripping) can be parameterized for
various SIMOCODE pro functions, such as overload. These are always displayed in tabular
form:
● "X" = Applicable
● "—" = Not applicable
● Default values are marked "d" for "default" in parentheses.
Warning X (d) X —
Deactivated X X X (d)
0 ... 25.5 s (default: 0)
Brief description of the responses:
● Tripping: The contactor controls QE* are tripped. A fault message is generated which is
available as a diagnosis via PROFIBUS DP. The fault message and the device-internal
signal remain on until the appropriate length of time has elapsed or the cause of the fault
has been eliminated and acknowledged.
● Warning: In addition to the device-internal signal, a warning signal is generated that is
available as diagnostics via the communication bus.
● Signaling: Only a device-internal signal is generated, which can be further processed as
required.
● Deactivated: The appropriate function is switched off, no signals are generated.
A delay time can also be set for specific responses.
Please read the operating instructions of the respective components. You can find the
operating instructions for SIMOCODE pro at Operating instructions
(www.siemens.com/sirius/manuals).