Parameters
4.2 Motor control
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
89
You will find detailed explanations of the settings in Chapter Application selection, settings
and definitions of control functions (Page 66).
Table 4- 15 Star-delta reversing starter settings
Star-delta reversing starter
Voltage display (in the device
Select "Line-to-line voltage"
Motor control → Control function:
OFF Control command OFF
Connection with any socket, usually with "Enabled control command OFF" socket
ОN > Control command ON >
Connection with any socket, usually with "Enabled control command ON >"
ON < Control command ON <
Connection with any socket, usually with "Enabled control command ON <"
FB ON "Feedback ON" auxiliary control input
Connection with any socket, usually with "Status - current flowing" socket
Non-maintained command mode
• Deactivated (default setting)
• Activated
Saving change-over command
• Deactivated (default setting)
• Activated
Separate fail-safe function from control
function
• Deactivated (default setting): A safety-related tripping by the DM-F modules
also affects the SIMOCODE pro control function, avoiding additional follow-on
fault messages. This setting is selected for applications where safety-related
tripping directly affects the motor controlled by SIMOCODE pro.
• Activated: A safety-related tripping by the DM-F modules does not affect the
SIMOCODE pro control function. This setting is selected for applications
where safety-related tripping does not affect the motor controlled by
SIMOCODE pro.
Load type You can choose between:
• Motor (default)
• Resistive load (see Chapter Application selection, settings and definitions of
control functions (Page 66))
Range 0 to 25.5 s (default: 0.5 s)
Range 0 to 6553.5 s (default: 1 s)
Range 0 to 655.3 s (10 ms steps) (default: 0 s)
Range 0 to 255 s (default: 0 s)