Parameters
4.2 Motor control
SIMOCODE pro - Parameterize
Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
91
Change-over pause
The "Change-over pause" parameter can be used to delay switching from "FAST" "SLOW"
to give the motor enough time to run down.
Note
Two current settings must be set for this control function:
I
s
1 for the SLOW speed
I
s
2 for the FAST speed.
Depending on the current range, the current can in many cases be directly measured at both
speeds with a single current transformer. Otherwise you will need two external current
transformers appropriate for the relevant speed (e.g. 3UF18 with a 1
A secondary
transformer rated current), whose secondary cables must lead through th
e current
measuring module within the range 0.3
to 3 A. The current setting I
s
1 or I
s
2 must be
converted according to the secondary currents of the external transformers.
For more
information, see Chapter
Overload protection (Page 34).
Schematic
Figure 4-20 Schematic of the "Dahlander" control function, "Protection / Control" function block

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE pro
CategoryControl Unit
LanguageEnglish

Related product manuals