Parameters
4.2 Motor control
SIMOCODE pro - Parameterize
96 Operating Manual, 04/2017, A5E40507630002A/RS-AA/001
You will find detailed explanations of the settings in Chapter Application selection, settings
and definitions of control functions (Page 66).
Table 4- 17 Control function settings for Dahlander reversing starter
Dahlander reversing starter
OFF Control command OFF (Connection with any socket, usually with "Enabled
control command OFF" socket)
ON Control command ON > (CW, SLOW) (connection with any socket, usually with
"Enabled control command ON >" socket)
ON >> Control command ON >> (CW, FAST) (connection with any socket, usually with
"Enabled control command ON >>" socket)
ON < Control command ON < (CCW, SLOW) (connection with any socket, usually
with "Enabled control command - ON <" socket)
ON << Control command ON << (CCW, FAST) (connection with any socket, usually
with "Enabled control command ON <<" socket)
FB ON Auxiliary control input "Feedback ON" (connection with any socket, usually with
"Status - current flowing" socket)
Non-maintained command mode
• Deactivated (default setting)
• Activated
Saving change-over command
• Deactivated (default setting)
• Activated
Separate fail-safe function from control
function
• Deactivated (default setting): A safety-related tripping by the DM-F modules
also affects the SIMOCODE pro control function, avoiding additional follow-
on fault messages. This setting is selected for applications where safety-
related tripping directly affects the motor controlled by SIMOCODE pro.
• Activated: A safety-related tripping by the DM-F modules does not affect the
SIMOCODE pro control function. This setting is selected for applications
where safety-related tripping does not affect the motor controlled by
SIMOCODE pro
Load type You can choose between:
• Motor (default)
• Resistive load (see Chapter Application selection, settings and definitions of
control functions (Page 66))
Range 0 to 25.5 s (default: 0.5 s)
Range 0 to 6553.5 s (default: 1.0 s)
Range 0 to 255 s (default: 0 s)
Range 0 to 655.3 s (10 ms steps) (default: 0.00 s)