APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 31 of 62
0: Warn; 1: Shutdown; 2: No action
Shutdown when external sensor
temperature is higher than this
value. Detecting only after safety
delay is over. The delay value can
be set.
Warn when external sensor
temperature is higher than this
value. Detecting only after safety
delay is over. The delay value and
return value can be set.
Users should set the corresponding
curve when select resistor curve
type or current curve type.
0: Warn; 1: Shutdown; 2: No action
Shutdown when external oil
pressure is lower than this value.
Detecting only after safety delay is
over. The delay value can be set.
Warn when external oil pressure is
higher than this value. Detecting
only after safety delay is over. The
delay value and return value can be
set.
Users should set the corresponding
curve when select resistor curve
type or current curve type.
0:Warn; 1:Shutdown; 2:No action
Warn when external level is lower
than this value. It is detecting all the
time. The delay value and return
value can be set.
Users should set the corresponding