StorEdge Single Phase Inverter with
Connection Unit for High Power - Technical
Specifications
114
SolarEdge-StorEdge Specification MAN-01-00275-1.0
SE7600A-US
1
Unit
Lower Power Output Higher Power Output
OUTPUT - AC (LOADS/GRID)
Rated AC Power Output 7600 VA
8350 VA
211-240-264 Vac
Max AC Power Output
AC Output Voltage Min-Nom-Max (L-
L)
2
AC Frequency Min-Nom-Max (1) 59.3 - 60 - 60.5 Hz
Maximum Continuous Output Current
@240V
32 A
GFDI 1 A
Utility Monitoring, Islanding Protection,
Country Configurable Thresholds
Yes
Charge Battery from AC (if Allowed)
THD %
Power factor with rated power
Typical Nighttime Power Consumption
Yes
< 3
>0.99 (configurable; 0.9 leading to 0.9 lagging)
<5 W
OUTPUT - AC (BACKUP POWER)
3
Rated AC Power Output 5000
4
VA
6600
4
VAMax AC Power Output - Surge
AC Output Voltage Min-Nom-Max (L-L) 211-240-264 Vac
AC Output Voltage Min-Nom-Max (L-N) 105-120-132 Vac
AC Frequency Min-Nom-Max 55 - 60 - 65 Hz
Maximum Continuous Output Current
@240V - Backup Mode
21 A
Max Continuous Output Current per
Phase @120V
25 A
GFDI A
AC Circuit Breaker
THD %
Power factor with rated power
1
Yes
< 5
0.2 leading to 0.2 lagging
1
These specifications apply to inverters with part numbers SE7600A-USS2XXXXX and connection unit model number
BCU-1PH-USS.
2
For other regional settings, contact SolarEdge Support.
3
Not designed for standalone applications and requires AC for commissioning.w
4
The rated AC power output is the minimum between the AC Power Output and the battery continuous peak power.