EasyManuals Logo
Home>SolarEdge>Inverter>storedge

SolarEdge storedge User Manual

SolarEdge storedge
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #96 background imageLoading...
Page #96 background image
Error code
LCD message Cause and Troubleshooting
CPU v3.18
and below
CPU v3.19
and above
196 2xC4
Backup init over
voltage
o
External voltage source on backed-up loads when
operating in Backup mode. Disconnect all external
voltage sources on backed-up loads.
o
Inverter internal error. Contact SolarEdge support.
0x2010 Internal CB down
Make sure that the loads do not consume higher
current than the inverter max output current. Open the
inverter StorEdge Connection Unit and switch the
main circuit breaker to the ON position.
System Warnings
Warningsaredisplayedintheinitialstatusscreenwiththeformat:<WarningX>.Forexample:
V a c [ V ] V d c [ V ] P a c [ W ]
1 . 0 0 . 5 0 . 0
P _ O K : X X X / Y Y Y < S _ O K >
W a r n i n g 8 O N
Thewarningisastatusscreen.Toviewthewarningdescription,presstheLCDbutton.
Thefollowingisalistofsystemwarnings:
Warning #
LCD text Comments and troubleshooting
CPU v3.18xx
and before
CPU v3.19xx
and later
1-4, 6-7
8x66 - 8x69
8x6A - 8x6F
Fan # Failure Clean or replace the fan
5 Turn Switch Off to Configure
Appears when trying to access the
Setup menus during production
8 2x111 Connection Unit Low 9V Battery
Replace the 9V battery in the StorEdge
Connection Unit. Refer to 9V Battery
Replacement on page 99.
Appendix A: Troubleshooting
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.2
95

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SolarEdge storedge and is the answer not in the manual?

SolarEdge storedge Specifications

General IconGeneral
BrandSolarEdge
Modelstoredge
CategoryInverter
LanguageEnglish

Related product manuals