Step 1: Activating the System
1. VerifythattheinverterON/OFFswitchisOFF.
2. MovetheStorEdgeConnectionUnitON/OFFswitchtotheOFFposition.
3.
Removetheinvertercover:Opentheinvertercover’ssixAllenscrewsandcarefullypullthecover
horizontallybeforeloweringit.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover is
removed.
RISQUE D’ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de
l'onduleur est retiré.
4.
Activatetheinverter:
a. VerifythatthecardS/NmatchestheinverterS/N.
b. Insertthecardintothe"CARD"slotonthecommunicationboard.
c. TurnONtheACswitchofthemaincircuitboard.
d. LCDshows:Running Script...è Done!
Figure 27: Activation card
IfLCDshows:Failed:
l TurnACOFFandON(reset),andrepeattheactivationprocess.
l Usetheactivationcodethatappearsonthecertificationinverterlabeltomanuallyactivatethe
inverter.
l Iftheproblempersists,contactSolarEdgeSupport.
NOTE
Youcanusetheactivationcodethatappearsonthecertificationinverterlabelto
activatetheinverterincaseofascripterrororamissingactivationcard.
Chapter 6: Commissioning the Installation
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.2
45