8 1600XPi Series UPS Installation and Operation Manual – 60616-014
4 Inspection/Storage/Disposal
4.1 Inspection
Inspect for shipping damage upon receipt of the UPS. Use caution when removing the unit from the pallet. Refer to labels
or documentation attached to packing material.
4.2 Unpacking
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping, keep all
original crating and packing materials for return to the shipping agent. The warranty does not apply to damage incurred
during shipping. Ensure that the rated capacity and the model number specied on the nameplate conform to the order
specications.
4.3 Storage
During periods of non-use, the following guidelines are recommended for storage.
Storage Preparation
Power up the UPS and allow it to operate with no load for 24 hours to fully charge the batteries.
Stop the unit (see Stop Operation on page 16).
Place the MCCB switch (see Appendix C for location) in the O󰀨 position.
Storing Conditions
For best results, store the UPS in the original shipping container and place on a wood or metal pallet.
Storage temperature: -4 – 104 °F (-20 – 40 °C).
The optimum storage temperature is 70 °F (21 °C). A higher ambient temperature will require recharging more
frequently during storage.
Avoid storage locations that:
Are subject to extreme temperature changes or high humidity.
Are subject to high levels of dust or metal particles.
Are subject to excessive vibration.
Have inclined oor surfaces.
Storage Maintenance
If stored at an ambient temperature less than 68 °F (20 °C), recharge the batteries every 9 months.
If stored at an ambient temperature of 68 – 86 °F (20 – 30 °C), recharge the batteries every 6 months.
If stored at an ambient temperature of 86 – 104 °F (30 – 40 °C), recharge the batteries every 3 months.
4.4 Disposal
Contact your local or state environmental agency for details on disposal of electrical components and packaging in your
particular area.
It is illegal to dump lead-acid batteries in landlls or dispose of improperly.
NOTE: Battery Pack cases are ABS Plastic No. 7.
Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call
Toshiba toll-free at (877) 867-8773 for more information about recycling.