60 1600XPi Series UPS Installation and Operation Manual – 60616-014
Display Recorded Meaning Action
OL110 N Overload – UPS is overloaded
(110% and above) Unit will switch
to bypass operation or shut down
if no action is taken.
Shut down excess equipment to reduce load.
REYEERR N Communication Error between
RemotEye and UPS.
Ensure RemotEye is connected to UPS. Call
Toshiba for service.
RS232ERR N Communication Error at Service
Port.
Call Toshiba for service.
REYEUER N Communication Error at LAN. Call Toshiba for service.
VDCUVBT N DC Bus Undervoltage During Bat-
tery Test.
Call Toshiba for service.
VIOV N Input Overvoltage – Input voltage
exceeds UPS specications.
UPS in On-Line Mode: UPS switches to BACKUP
mode until Input Voltage returns to normal. Check
bypass power.
VIUV N Input Undervoltage – Input voltage
less than UPS specications.
UPS in On-Line Mode: UPS switches to BACKUP
mode until Input Voltage returns to normal. Check
bypass power.
23.5 System Mode Messages
A UPS Mode message is generated when the UPS changes operating mode. The following tables list the possible operat-
ing modes for the UPS.
Display Meaning
Backup Backup – Power comes from other than input.
BattTest Battery Test – Battery test in progress.
Bypass Bypass – UPS is o󰀪ine, power is being provided directly from UPS input.
On–Line On-Line – Input converter and inverter are running (Double conversion mode).
Shutdown Shutdown – No output, DC Bus is charged through Softstart Resistor.
Startup Startup – UPS is starting up.
23.6 System Status Messages
A UPS Status message is generated when the UPS changes its status (from inverter to bypass mode, for example). The
table below shows the possible Status messages and their meaning.
Display Meaning Action
BYP Bypass mode – Power is supplied by UPS input. No action needed.
CHRGERR Charger Error – Charger overvoltage error. Call Toshiba for service.
DLYST Delay Start – UPS is counting down prior to
startup.
No action needed.
EE1ST EEPROM is loaded with default values. No action needed.
EE2RAERR EEPROM to RAM loading Error. Call Toshiba for service.
EEUPERR EEPROM updating Error. Call Toshiba for service.

Table of Contents