ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 91 of 140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon SNVT
Lon Direction
Modbus
Address
Blr Addr 2
2
Comm Address
SMD_BAS_IP_HTR_02_[0]
AV:400
Data Float
66
nvoHTR_02_1
inc count (9)
Output (non-polled)
30400
2
Unit Status
SMD_BAS_IP_HTR_02_[1]
AV:401
Data Float
67
nvoHTR_02_2
inc count (9)
Output (non-polled)
30401
2
Fault Code
SMD_BAS_IP_HTR_02_[2]
AV:402
Data Float
68
nvoHTR_02_3
inc count (9)
Output (non-polled)
30402
2
Outlet Temp
SMD_BAS_IP_HTR_02_[3]
AV:403
Data Float
69
nvoHTR_02_4
inc count (9)
Output (non-polled)
30403
2
FFWD Temp
SMD_BAS_IP_HTR_02_[4]
AV:404
Data Float
70
nvoHTR_02_5
inc count (9)
Output (non-polled)
30404
2
Inlet Temp
SMD_BAS_IP_HTR_02_[5]
AV:405
Data Float
71
nvoHTR_02_6
inc count (9)
Output (non-polled)
30405
2
Exhaust Temp
SMD_BAS_IP_HTR_02_[6]
AV:406
Data Float
72
nvoHTR_02_7
inc count (9)
Output (non-polled)
30406
2
Air Temp
SMD_BAS_IP_HTR_02_[7]
AV:407
Data Float
73
nvoHTR_02_8
inc count (9)
Output (non-polled)
30407
2
Flame Strength
SMD_BAS_IP_HTR_02_[8]
AV:408
Data Float
74
nvoHTR_02_9
inc count (9)
Output (non-polled)
30408
2
Fire Rate In
SMD_BAS_IP_HTR_02_[9]
AV:409
Data Float
75
nvoHTR_02_10
inc count (9)
Output (non-polled)
30409
2
Fire Rate Out
SMD_BAS_IP_HTR_02_[10]
AV:410
Data Float
76
nvoHTR_02_11
inc count (9)
Output (non-polled)
30410
2
Unit Type
SMD_BAS_IP_HTR_02_[11]
AV:411
Data Float
77
nvoHTR_02_12
inc count (9)
Output (non-polled)
30411
2
Unit Size
SMD_BAS_IP_HTR_02_[12]
AV:412
Data Float
78
nvoHTR_02_13
inc count (9)
Output (non-polled)
30412
2
Value State
SMD_BAS_IP_HTR_02_[13]
AV:413
Data Float
79
nvoHTR_02_14
inc count (9)
Output (non-polled)
30413
2
Net Remote Setpt
SMD_BAS_IP_HTR_02_[14]
AV:414
Data Float
80
nvoHTR_02_15
inc count (9)
Output (non-polled)
30414
2
Run Cycles Upper
SMD_BAS_IP_HTR_02_[15]
AV:415
Data Float
81
nvoHTR_02_16
inc count (9)
Output (non-polled)
30415
2
Run Cycles Lower
SMD_BAS_IP_HTR_02_[16]
AV:416
Data Float
82
nvoHTR_02_17
inc count (9)
Output (non-polled)
30416
2
Run Hours Upper
SMD_BAS_IP_HTR_02_[17]
AV:417
Data Float
83
nvoHTR_02_18
inc count (9)
Output (non-polled)
30417
2
Run Hours Lower
SMD_BAS_IP_HTR_02_[18]
AV:418
Data Float
84
nvoHTR_02_19
inc count (9)
Output (non-polled)
30418
2
Oxygen Level
SMD_BAS_IP_HTR_02_[19]
AV:419
Data Float
85
nvoHTR_02_20
inc count (9)
Output (non-polled)
30419
Blr Addr 3
3
Comm Address
SMD_BAS_IP_HTR_03_[0]
AV:500
Data Float
86
nvoHTR_03_1
inc count (9)
Output (non-polled)
30500
3
Unit Status
SMD_BAS_IP_HTR_03_[1]
AV:501
Data Float
87
nvoHTR_03_2
inc count (9)
Output (non-polled)
30501