EasyManuals Logo
Home>Watts>Gateway>Aerco ProtoNode FPC-N34

Watts Aerco ProtoNode FPC-N34 User Manual

Watts Aerco ProtoNode FPC-N34
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #92 background imageLoading...
Page #92 background image
ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 92 of 140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon SNVT
Lon Direction
Modbus
Address
3
Fault Code
SMD_BAS_IP_HTR_03_[2]
AV:502
Data Float
88
nvoHTR_03_3
inc count (9)
Output (non-polled)
30502
3
Outlet Temp
SMD_BAS_IP_HTR_03_[3]
AV:503
Data Float
89
nvoHTR_03_4
inc count (9)
Output (non-polled)
30503
3
FFWD Temp
SMD_BAS_IP_HTR_03_[4]
AV:504
Data Float
90
nvoHTR_03_5
inc count (9)
Output (non-polled)
30504
3
Inlet Temp
SMD_BAS_IP_HTR_03_[5]
AV:505
Data Float
91
nvoHTR_03_6
inc count (9)
Output (non-polled)
30505
3
Exhaust Temp
SMD_BAS_IP_HTR_03_[6]
AV:506
Data Float
92
nvoHTR_03_7
inc count (9)
Output (non-polled)
30506
3
Air Temp
SMD_BAS_IP_HTR_03_[7]
AV:507
Data Float
93
nvoHTR_03_8
inc count (9)
Output (non-polled)
30507
3
Flame Strength
SMD_BAS_IP_HTR_03_[8]
AV:508
Data Float
94
nvoHTR_03_9
inc count (9)
Output (non-polled)
30508
3
Fire Rate In
SMD_BAS_IP_HTR_03_[9]
AV:509
Data Float
95
nvoHTR_03_10
inc count (9)
Output (non-polled)
30509
3
Fire Rate Out
SMD_BAS_IP_HTR_03_[10]
AV:510
Data Float
96
nvoHTR_03_11
inc count (9)
Output (non-polled)
30510
3
Unit Type
SMD_BAS_IP_HTR_03_[11]
AV:511
Data Float
97
nvoHTR_03_12
inc count (9)
Output (non-polled)
30511
3
Unit Size
SMD_BAS_IP_HTR_03_[12]
AV:512
Data Float
98
nvoHTR_03_13
inc count (9)
Output (non-polled)
30512
3
Value State
SMD_BAS_IP_HTR_03_[13]
AV:513
Data Float
99
nvoHTR_03_14
inc count (9)
Output (non-polled)
30513
3
Net Remote Setpt
SMD_BAS_IP_HTR_03_[14]
AV:514
Data Float
100
nvoHTR_03_15
inc count (9)
Output (non-polled)
30514
3
Run Cycles Upper
SMD_BAS_IP_HTR_03_[15]
AV:515
Data Float
101
nvoHTR_03_16
inc count (9)
Output (non-polled)
30515
3
Run Cycles Lower
SMD_BAS_IP_HTR_03_[16]
AV:516
Data Float
102
nvoHTR_03_17
inc count (9)
Output (non-polled)
30516
3
Run Hours Upper
SMD_BAS_IP_HTR_03_[17]
AV:517
Data Float
103
nvoHTR_03_18
inc count (9)
Output (non-polled)
30517
3
Run Hours Lower
SMD_BAS_IP_HTR_03_[18]
AV:518
Data Float
104
nvoHTR_03_19
inc count (9)
Output (non-polled)
30518
3
Oxygen Level
SMD_BAS_IP_HTR_03_[19]
AV:519
Data Float
105
nvoHTR_03_20
inc count (9)
Output (non-polled)
30519
Blr Addr 4
4
Comm Address
SMD_BAS_IP_HTR_04_[0]
AV:600
Data Float
106
nvoHTR_04_1
inc count (9)
Output (non-polled)
30600
4
Unit Status
SMD_BAS_IP_HTR_04_[1]
AV:601
Data Float
107
nvoHTR_04_2
inc count (9)
Output (non-polled)
30601
4
Fault Code
SMD_BAS_IP_HTR_04_[2]
AV:602
Data Float
108
nvoHTR_04_3
inc count (9)
Output (non-polled)
30602
4
Outlet Temp
SMD_BAS_IP_HTR_04_[3]
AV:603
Data Float
109
nvoHTR_04_4
inc count (9)
Output (non-polled)
30603
4
FFWD Temp
SMD_BAS_IP_HTR_04_[4]
AV:604
Data Float
110
nvoHTR_04_5
inc count (9)
Output (non-polled)
30604

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts Aerco ProtoNode FPC-N34 and is the answer not in the manual?

Watts Aerco ProtoNode FPC-N34 Specifications

General IconGeneral
BrandWatts
ModelAerco ProtoNode FPC-N34
CategoryGateway
LanguageEnglish