9.2 Adding setting groups
In order to show for a DNP master which setting group is used, the following
procedure can be performed.
In this example, only setting groups one and two are used. The DNP master will get
two binary inputs: the first is set if setting group one is used, the second is set if setting
group two is used.
1. Configure ACTVGRP (Basic IED functions) and SP16GGIO (Monitoring) with
the Application Configuration Tool (ACT).
IEC11000423-1-en.vsd
IEC11000423 V1 EN
Figure 73: Application configuration tool
To make it easier to recognize the signals for the active setting
group, the user-defined names are used.
2. Open the Communication Management Tool (CMT). Set the Signal Type to
Binary Input Object and choose the connection of the master for which the values
should be presented.
Section 9 1MRK 511 284-UEN A
DNP3 communication engineering
106 650 series
Engineering manual