IEC08000271.vsd
Execution order
group 1
Execution order
group 2
Execution order
group 3
Execution Flow
IEC08000271 V1 EN
Figure 36: ACT: Concept of Execution order sequence
In the conceptual MainApplication example in Figure 36, the execution order of the
main function block in the execution order group 2 defines the execution orders
needed in group 1 and 3. The preceding logic done with function blocks in group 1
must have a lower execution order than the ones in group 2. The following function
blocks in group 3 must have a higher execution order than the main function block in
group 2.
5.1.5 Configuration parameters
Configuration parameters are found in the parameter setting tool. For example, the
SMAI function block has to be configured to support AC-current values or AC-
voltage values.
5.1.6 Connections and variables
A connection is the link or "wire" between function block outputs and inputs.
Rules and methods to do connections:
Drag a line between two signals.
Link two signals by using variables.
It is possible to search and replace variable names in ACT.
Connection validation
A connection is only useful and possible between two signals of the same data type,
see Figure 37.
1MRK 511 284-UEN A Section 5
Protection and control engineering
650 series 55
Engineering manual

Table of Contents

Other manuals for ABB 650 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 650 series and is the answer not in the manual?

ABB 650 series Specifications

General IconGeneral
BrandABB
Model650 series
CategoryController
LanguageEnglish

Related product manuals