EasyManuals Logo
Home>ABB>Adapter>AC31

ABB AC31 User Manual

ABB AC31
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
Fig. 53: Process voltage connections - 07DC92-AD
NOTICE!
Process voltage must always be connected to connector X4 on device 07DC92-
AD.
Connector X4 also supplies the internal electronics for the device 07DC92-AD with 0.15 A.
Process voltage connections (X2, X3, X5, X6):
Maximum current for digital outputs X2 + X3: 4 A / 4 to
Maximum current for digital outputs X5 + X6: 4 A / 4 to
Input currents > 4 A require the connection of the second L+ contact of con-
nector X4.
For input currents > 8 A, additional L+ contacts from X2, X3, X5 or X6 must
be used.
The L+ contacts for the connectors X2, X3, X5 or X6 may be loaded with a
maximum of 4 A.
1.5.2.8.2 Technical details of the I/O channels as binary inputs
Data Value
Connections X2 / 1.0 to 1.7
X3 / 2.0 to 2.7
X5 / 3.0 to 3.7
X6 / 4.0 to 4.7
Input type according to EN 61131-2 Type 1 (realized through resistors)
AC31 Adapters
Replacement devices: I/O modules > Replacement device 07DC92-AD
2018/09/243ADR010122, 8, en_US84

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB AC31 and is the answer not in the manual?

ABB AC31 Specifications

General IconGeneral
BrandABB
ModelAC31
CategoryAdapter
LanguageEnglish

Related product manuals