158 Parameters
Other [bit] Source selection (see Terms and abbreviations on page 64). -
79.18 Tank high sensor Selects the source for tank high level sensor enable signal.
0 = Not selected.
1 = Selected.
See parameter 79.17 Tank low sensor.
DI6
79.31 Pump start time Defines the pump start time. This feature is used with timed
function.
Note: Timed function must be enabled to use this feature.
See parameter 79.10 Operating mode.
00:00:00
00:00:00...
23:59:59
Pump start time. 1 = 1
79.32 Pump stop time Defines the pump stop time. This feature is used with timed
function.
Note: Timed function must be enabled to use this feature.
See parameter 79.10 Operating mode.
00:00:00
00:00:00...
23:59:59
Pump stop time. 1 = 1
79.40 MPPT reference Selects the source for MPPT reference enable signal.
0 = Disabled
1 = Enabled
Enable
Disable MPPT reference is not activated. 0
Enable MPPT reference is activated. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Other [bit] Source selection (see Terms and abbreviations on page 64). -
79.41 Start DC voltage Defines the minimum DC voltage to start the drive.
Note: If you change this value while the inverter is
running, the changed value is effective only during the
next start
225
225...800 V DC voltage. 1 = 1
79.42 PV cell min voltage Defines the minimum DC voltage below which the
drive cannot operate.
Note: The drive stops operating below this voltage.
225
225...800 V DC voltage. 1 = 1
79.43 PV cell max voltage Defines the maximum DC voltage. At any value above
this voltage, the drive trips due to D4B1 PV max volt
fault.
800
225...800 V DC voltage. 1 = 1
79.51 Pump minimum
speed
Defines the minimum motor speed. At any value below
this speed, the drive stops functioning and auto
restarts after the time defined in 79.61 Fault reset time. This
setting avoids unnecessary operation of pump at low speed.
200
0...3000 rpm Speed. 1 = 1
No. Name/Value Description Def/FbEq16
ACQ80 FW.book Page 158 Thursday, February 14, 2019 11:33 AM

Table of Contents

Other manuals for ABB ACQ80-04

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACQ80-04 and is the answer not in the manual?

ABB ACQ80-04 Specifications

General IconGeneral
BrandABB
ModelACQ80-04
CategoryDC Drives
LanguageEnglish

Related product manuals