222 Actual signals and parameters
x…x Setting range depends on parameter 3204 SUPERV 2
PARAM setting.
-
3206 SUPERV 2 LIM
HI
Defines the high limit for the second supervised signal
selected by parameter 3204 SUPERV 2 PARAM.
Supervision wakes up if the value is above the limit.
-
x…x Setting range depends on parameter 3204 SUPERV 2
PARAM setting.
-
3207 SUPERV 3
PARAM
Selects the third supervised signal. Supervision limits are
defined by parameters 3208 SUPERV 3 LIM LO and 3209
SUPERV 3 LIM HI. See parameter 3201 SUPERV 1
PARAM.
105
x…x Parameter index in group 01 OPERATING DATA. For
example, 102 = 0102 SPEED.
1 = 1
3208 SUPERV 3 LIM
LO
Defines the low limit for the third supervised signal selected
by parameter 3207 SUPERV 3 PARAM. Supervision wakes
up if the value is below the limit.
-
x…x Setting range depends on parameter 3207 SUPERV 3
PARAM setting.
-
3209 SUPERV 3 LIM
HI
Defines the high limit for the third supervised signal selected
by parameter 3207 SUPERV 3 PARAM. Supervision wakes
up if the value is above the limit.
-
x…x Setting range depends on parameter 3207 SUPERV 3
PARAM setting.
-
33 INFORMATION Firmware package version, test date etc.
3301 FIRMWARE Displays the version of the firmware package.
0000…FFFF
hex
For example, 241A hex
3302 LOADING
PACKAGE
Displays the version of the loading package. type
dependent
2101…21FF
hex
2101 hex = ACS310-03E-
2102 hex = ACS310-03U-
3303 TEST DATE Displays the test date. 00.00
Date value in format YY.WW (year, week)
3304 DRIVE RATING Displays the drive current and voltage ratings. 0000 hex
0000…FFFF
hex
Value in format XXXY hex:
XXX = Nominal current of the drive in amperes. An “A”
indicates decimal point. For example if XXX is 9A7, nominal
current is 9.7 A.
Y = Nominal voltage of the drive:
1 = 1-phase 200…240 V
2 = 3-phase 200…240 V
4 = 3-phase 380…480 V
3305 PARAMETER
TABLE
Displays the version of the parameter table used in the
drive.
0000…FFFF
hex
Eg 400E hex
All parameters
No. Name/Value Description Def/FbEq