260 Actual signals and parameters
5303 EFB BAUD
RATE
Defines the transfer rate of the link. 9.6 kbit/s
1.2 kbit/s 1.2 kbit/s 1 =
0.1 kbit/s
2.4 kbit/s 2.4 kbit/s
4.8 kbit/s 4.8 kbit/s
9.6 kbit/s 9.6 kbit/s
19.2 kbit/s 19.2 kbit/s
38.4 kbit/s 38.4 kbit/s
57.6 kbit/s 57.6 kbit/s
76.8 kbit/s 76.8 kbit/s
5304 EFB PARITY Defines the use of parity and stop bit(s) and the data length.
The same setting must be used in all on-line stations.
8 NONE 1
8 NONE 1 No parity bit, one stop bit, 8 data bits 0
8 NONE 2 No parity bit, two stop bits, 8 data bits 1
8 EVEN 1 Even parity indication bit, one stop bit, 8 data bits 2
8 ODD 1 Odd parity indication bit, one stop bit, 8 data bits 3
5305 EFB CTRL
PROFILE
Selects the communication profile. See section
Communication profiles on page 302.
ABB DRV
LIM
ABB DRV LIM ABB drives limited profile 0
DCU PROFILE DCU profile 1
ABB DRV
FULL
ABB drives profile 2
5306 EFB OK
MESSAGES
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
0
0…65535 Number of messages 1 = 1
5307 EFB CRC
ERRORS
Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note: High electromagnetic noise levels generate errors.
0
0…65535 Number of messages 1 = 1
5308 EFB UART
ERRORS
Number of messages with a character error received by the
drive
0
0…65535 Number of messages 1 = 1
5309 EFB STATUS Status of the EFB protocol IDLE
IDLE EFB protocol is configured, but not receiving any messages. 0
EXECUT INIT EFB protocol is initializing. 1
TIME OUT A time out has occurred in the communication between the
network master and the EFB protocol.
2
CONFIG
ERROR
EFB protocol has a configuration error. 3
OFF-LINE EFB protocol is receiving messages that are NOT
addressed to this drive.
4
ON-LINE EFB protocol is receiving messages that are addressed to
this drive.
5
All parameters