Actual signals and parameters 197
DI2(INV) See selection DI1(INV).-2
DI3(INV) See selection DI1(INV).-3
DI4(INV) See selection DI1(INV).-4
DI5(INV) See selection DI1(INV).-5
1609 START
ENABLE 2
Selects the source for the Start enable 2 signal. See
parameter 1608 START ENABLE 1.
NOT SEL
See parameter 1608 START ENABLE 1.
1610 DISPLAY
ALARMS
Activates/deactivates alarms OVERCURRENT (2001),
OVERVOLTAGE (2002), UNDERVOLTAGE (2003) and
DEVICE OVERTEMP (2009). For more information, see
chapter Fault tracing on page 311.
NO
NO Alarms are inactive. 0
YES Alarms are active. 1
1611 PARAMETER
VIEW
Selects the parameter view, ie which parameters are shown
on the control panel.
Note: For embedded modbus, LONG VIEW (3) must be
selected.
SHORT
VIEW
FLASHDROP Shows the FlashDrop parameter list. Does not include the
short parameter list. Parameters which are hidden by the
FlashDrop device are not visible.
FlashDrop is designed for fast copying of parameters to
unpowered drives. It allows easy customization of the
parameter list, eg selected parameters can be hidden. For
more information, see MFDT-01 FlashDrop user’s manual
(3AFE68591074 [English]).
FlashDrop parameter values are activated by setting
parameter 9902 APPLIC MACRO to 31 (LOAD FD SET).
1
SHORT VIEW Shows only a subset of all signals and parameters. See
section Actual signals in the short parameter view
on page
167 and Parameters in the short parameter view on page
167.
2
LONG VIEW Shows all signals (section All actual signals
on page 170)
and parameters (this table, starting on page 177).
3
1612 FAN
CONTROL
Selects the heat sink fan On/Off control for forcing the
cooling fan of the drive constantly On.
AUTO
AUTO Automatic fan control 0
ON Fan is always On 1
18 FREQ IN & TRAN
OUT
Frequency input and transistor output signal processing.
1801 FREQ INPUT
MIN
Defines the minimum input value when DI5 is used as a
frequency input. See section Frequency input on page 127.
0Hz
0…16000 Hz Minimum frequency 1 = 1 Hz
1802 FREQ INPUT
MAX
Defines the maximum input value when DI5 is used as a
frequency input. See section Frequency input on page 127.
1000 Hz
0…16000 Hz Maximum frequency 1 = 1 Hz
1803 FILTER FREQ
IN
Defines the filter time constant for frequency input, that is,
the time within which 63% of a step change is reached. See
section Frequency input on page 127.
0.1 s
All parameters
No. Name/Value Description Def/FbEq
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Other manuals for ABB ACS310

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS310 and is the answer not in the manual?

ABB ACS310 Specifications

General IconGeneral
BrandABB
ModelACS310
CategoryDC Drives
LanguageEnglish

Related product manuals