Maintenance and hardware diagnostics 329
15
Maintenance and hardware
diagnostics
What this chapter contains
The chapter contains preventive maintenance instructions and LED indicator
descriptions.
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance.
The table lists the routine maintenance intervals recommended by ABB.
Consult your local ABB Service representative for more details on the maintenance.
On the Internet, go to http://www.abb.com/drives
and select Drive Services –
Maintenance and Field Services.
Maintenance Interval Instruction
Reforming of capacitors Every year when
stored
See Capacitors on page 331.
Check of dustiness, corrosion
and temperature
Every year
Replacement of the cooling fan
(frame sizes R1…R4)
Every three years See Cooling fan on page 330.
Check and tightening of the
power terminals
Every six years See Power connections on page 332.
Replacement of the battery in
the Assistant control panel
Every ten years See Changing the battery in the
Assistant control panel on page 332.
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Other manuals for ABB ACS310

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS310 and is the answer not in the manual?

ABB ACS310 Specifications

General IconGeneral
BrandABB
ModelACS310
CategoryDC Drives
LanguageEnglish

Related product manuals