78 Control panels
Copy mode
The Basic control panel can store a full set of drive parameters and up to two user
sets of drive parameters to the control panel. Uploading and downloading can be
performed in local control. The control panel memory is non-volatile.
In the Copy mode, you can do the following:
• Copy all parameters from the drive to the control panel (uL – Upload). This
includes all defined user sets of parameters and internal (not adjustable by the
user) parameters.
• Restore the full parameter set from the control panel to the drive (dL A –
Download all). This writes all parameters, including the internal non-user-
adjustable motor parameters, to the drive. It does not include the user sets of
parameters.
Note: Only use this function to restore a drive, or to transfer parameters to
systems that are identical to the original system.
• Copy a partial parameter set from the control panel to a drive (dL P – Download
partial). The partial set does not include user sets, internal motor parameters,
parameters 9905…9909, 1605, 1607, 5201, nor any group 53 EFB PROTOCOL
parameters.
The source and target drives and their motor sizes do not need to be the same.
• Copy user set 1 parameters from the control panel to the drive (dL u1 – Download
user set 1). A user set includes group 99 START-UP DATA parameters and the
internal motor parameters.
The function is only shown on the menu when User set 1 has been first saved
using parameter 9902 APPLIC MACRO (see section user macros on page 112)
and then uploaded to panel.
• Copy user set 2 parameters from the control panel to the drive (dL u2 – Download
user set 2). As dL u1 – Download User set 1 above.
• Start, stop, change the direction and switch between local and remote control.