150 Program features
User load curve
The user can specify a load curve (motor torque as a function of frequency) for
supervision. The curve is defined by five points. Supervision can be set for the torque
dropping below the underload curve, exceeding the overload curve, or both.
A fault is generated if the torque has been out of the allowed area for longer than the
user-defined time limit. An alarm is generated if the torque has been out of the
allowed area for longer than the half of the user-defined time limit.
Settings
Diagnostics
Parameter Additional information
Group 37 USER LOAD CURVE User load curve settings
Actual signal Additional information
0105 Motor torque
Alarm
USER LOAD CURVE Out of allowed area for longer than half of the defined
time limit
Fault
USER LOAD CURVE Out of allowed area for longer than the defined time
limit
PAR USER LOAD C Incorrect user load curve parameter setting
(3704 > 3707 or 3707 > 3710 or 3710 > 3713 or 3713 >
3716 or
3705 > 3706 or 3708 > 3709 or 3711 > 3712 or 3714 >
3715 or 3717 > 3718)
Overload area
Underload area
Allowed operating area
Motor torque (%)
Output
frequency (Hz)
Freq. 2 Freq. 1 Freq. 3 Freq. 4 Freq. 5
Torque
high 1
Torque
high 2
Torque
high 3
Torque
low 1
Torque
low 2
Torque
low 3
Torque
high 4
Torque
low 4
Torque
high 5
Torque
low 5
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Other manuals for ABB ACS310

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS310 and is the answer not in the manual?

ABB ACS310 Specifications

General IconGeneral
BrandABB
ModelACS310
CategoryDC Drives
LanguageEnglish

Related product manuals